COMMUNICATION >> HILSCHER Fieldbus Master
FIELDBUS MASTER
netHOST FB - LAN controlled Fieldbus master for DIN rail
Fieldbus master for IT service & business networks
A netHOST FB is a full-featured and autonomously operating Fieldbus master allowing industrial PCs and other embedded systems the control of Fieldbus networks over an ordinary LAN connection.
A simple TCP/IP based transport protocol transfers the services between the controlling unit and the device. For device integration a DLL for Windows and a C source code for embedded solutions is provided. In both cases the call interface (API) is identical to Hilschers PC cards. This makes a netHOST a remotely controllable PC card for field installations.
100 bytes process data inputs and outputs are exchangeable over the LAN network in about one millisecond. Acyclic services to the subordinate Fieldbus stations are supported as well. A bus confi guration software is included in the delivery.
Two devices can be used in combination to realize redundant applications. Services are provided to execute a controlled switchover in the event one device fails or a line breaks. In case a device fails the memory card slot allows service personnel to perform a firmware and configuration recovery on a replacement device in less than a minute.
Highlights
-
Controlled via simple TCP/IP based access protocol
-
For PROFIBUS, CANopen and DeviceNet
-
Identical API as Fieldbus PC cards
-
With application example, TCP/IP
-
driver/coding and DLL as source code
-
In dual-mode applicable for redundancy operations
Article | FIELDBUS MASTER Description
|
---|
NHST-T100-EN/ECM
| netHOST EtherCAT Master
|
NHST-T100-DP/DPM
| netHOST PROFIBUS Master
|
NHST-T100-CO/COM
| netHOST CANopen Master
|
NHST-T100-DN/DNM
| netHOST DeviceNet Maste
|
NHST-T100-EN/PNM
| netHOST PROFINET Master
|
Technical Data
netHOST FB
|
|
---|
LAN Ethernet
| IEEE 802.3 10 / 100 Base-T, Open TCP / IP transport protocol, Port 50111 and 50112, 128 Bytes E and A in 1,33 ms typical |
Profibus Master | IEC 61158, DP, DPV1, Class 1 / Class 2 Master, 125 Slaves / 5736 Bytes I and O data |
CANopen-Master | EN 50325-4, SDO, PDO, NMT, SYNC EMCY, 126 Notes / 3854 Bytes I and O data, 11 Bit, 29Bit Identifier CAN Layer 2 |
DeviceNet-Master | IEC 62026-3, UCMM, Predefined Master / Slave Conn., COS, Poll, Cyclic I / O-Connection, 64 Slaves / 3854 Bytes I and O datan, Explicit Message Channel data access |
Technical Data
netHOST FB |
|
---|
Operating Temperature Storage Temperature Operating Voltage Dimensions (L x W x H) Weight Interfaces
Display Certification Emission Noise Immunity, Vibration, Shock Mounting Processor Card slot
| ±0°C... +60°C -40 °C... +85 °C +18... +30 V / 130 mA @ +24 V 100 x 52 x 70 mm (without connector) approx. 150 g USB Mini-B, 2 x RJ45, D-Sub DE-9 connector, COMBICON-5-pin SYS, APL, L/A, Rx / Tx, bus-specific UL 508, CE, RoHS, REACH EG Nr. 1907/2006 CISPR 11 Class A EN 61131-2:2003 DIN-Rail, EN-50022 35mm x 7,5mm netX 100 MMC card, SD card
|
The following figure illustrates the data flow of Ethernet Marshalling with the netHOST:
Data flow of LAN controlled netHOST device